(N)HXCH-J-SERVO FE180 PH90/E90 0,6/1 kV 4×35

Performance Characteristics

PN-EN50575
PN-EN50575
Indoor application
Indoor application
Outdoor application
Outdoor application
Sprinkler zones
Sprinkler zones
Functional integrity
Functional integrity
Circuit integrity E90 DIN VDE 4102-12
Circuit integrity E90 DIN VDE 4102-12
Flame retardant PN-EN 60332-1-2
Flame retardant PN-EN 60332-1-2
Halogen-free
Halogen-free
UV resistance
UV resistance

Application

TECHNOFLAME (N)HXCH-J-SERVO FE180 PH90/E90 0,6/1 kV fire resistant halogen free cables, are intended for connecting converters or inverters with motors in fire protection equipment which is to operate in fire conditions. The cables shall be applied in locations where, in case of fire, higher safety for human beings and expensive electronic equipment is required (subway tunnels, hospitals, shopping centres, supermarkets, cinemas, theatres, stadiums and other public buildings). Functions of the cables are maintained for 90 minutes – power is supplied to equipment which must operate in fire conditions and during fire fighting (e.g. water pumps in fire extinguishing systems, smoke removing fans, emergency lighting and elevators). The cables are certified by Scientific and Research Centre for Fire Protection - National Research Institute (Centrum Naukowo-Badawcze Ochrony Przeciwpożarowej - PIB) at Józefów. The cables are resistant to water in accordance with EN 50200 Annex E and can be used in fire protected rooms with fixed pressure water spraying fire extinguishing systems (sprinkler zones). The cables are flame retardant and their smoke emission is low, emitted fumes are non toxic and non corrosive. Cables are protected by a specially designed and highly effective collective shield against emission of electromagnetic interferences to environment and against influence of external interferences. The cables are suitable for fixed indoor and outdoor installations. Sheathing is UV radiation resistant. Laying cables in water or direct earth burial are only permitted if additional protection is used.

Structure

 
  • flexible, multiwire conductors, stranded of bare annealed copper wires (tin-plated on request), meeting require­ments of class 5 per PN-EN 60228,
  • double special cross-linked silicone rubber insulation - colours of insulation: black, brown, grey, green-yellow,
  • insulated conductors and fillers laid-up in a cable core,
  • cable core wrapped in polyester tape,
  • cable core wrapped in mica tape,
  • double screen incorporating aluminium-polyester tape under a tinned copper wire braid shield of coverage bigger than 80%,
  • orange cable sheath made of halogen free compound type HM4 according to HD 604 S1.
Conductor cross-section mm2 1,5 2,5 4 6 10 16 25 35 50
Maximum DC conductor resistance at 20°C Ω/km 13,3 7,98 4,59 3,3 1,91 1,21 0,78 0,554 0,386

Cable installation – should be carried out on a certified cable fastening system, in accordance with the National Technical Assessments (KOT) issued for fastening manufacturers. Only certified cable fixing systems, tested according to DIN 4102 part 12, should be used.

Characteristics Descritpion
Operating voltage Uo/U 0,6/1 kV
Voltage test 4 kV sk
Minimum insulation resistance, at90°C 1011 Ω∙cm
Inductance, approximate 0,7 mH/km
Shielding efficiency, approximate 75 dB
Conductor temperature limit in work conditions + 90°C
Conductor temperature limit at short-circuit + 250°C
Operating temperature range during operation from - 30 to + 90°C
Operating temperature range during installation from - 5 to + 70°C
Minimum bending radius Ø < 12 mm 5 x cable diameter
Minimum bending radius Ø = 12÷20 mm 7,5 x cable diameter
Minimum bending radius Ø > 20 mm 10 x cable diameter
Corrosivity of emitted gases per very low, halogen free PN-EN 60754-1, PN-EN 60754-2, IEC 60754-2
pH > 4,3
Conductivity < 2,5 μS/mm
Smoke density low smoke density PN-EN 61034-2, IEC 61034-2
Light transmittance, minimum. 60%
Cable combustibillity flame retardant
Combustibillity tests PN-EN 60332-1-2, IEC 60332-1-2, PN-EN 60332-3-24, IEC 60332-3-24,
Circuit integrity: E90 DIN 4102-12
Circuit integrity: PH90 PN-EN 50200, PN-EN 50362 or PN-EN IEC 60331-1
Insulation integrity FE180 IEC 60331-21, IEC 60331-11
Reference standards CNBOP-PIB-KOT-2021/0311-3701 wyd.3, WT-TK-44
Class reaction to fire ( PN-EN 13501-6) B2ca-s2,d1,a1
DoP declarations are available at technokabel.com.pl
The cable meets requirements of the low voltage direction 2014/35/UE
Item Index Item Name CPR Class Outer Diameter (approx.) mm Cable Weight (approx.) kg/km Cu Index
Item Index: 1669 004 33 Item Name: (N)HXCH-J-SERVO FE180 PH90/E90 0,6/1 kV 4×25 CPR Class: B2ca-s2,d1,a1 Outer Diameter (approx.) mm: 27.3 Cable Weight (approx.) kg/km: 1542 Cu Index: 1143.3
Item Index: 1669 005 33 Item Name: (N)HXCH-J-SERVO FE180 PH90/E90 0,6/1 kV 4×35 CPR Class: B2ca-s2,d1,a1 Outer Diameter (approx.) mm: 30.3 Cable Weight (approx.) kg/km: 1987 Cu Index: 1548.3
Item Index: 1669 006 33 Item Name: (N)HXCH-J-SERVO FE180 PH90/E90 0,6/1 kV 4×2,5 CPR Class: B2ca-s2,d1,a1 Outer Diameter (approx.) mm: 14.5 Cable Weight (approx.) kg/km: 313 Cu Index: 139.8
Item Index: 1669 007 33 Item Name: (N)HXCH-J-SERVO FE180 PH90/E90 0,6/1 kV 4×4 CPR Class: B2ca-s2,d1,a1 Outer Diameter (approx.) mm: 15.9 Cable Weight (approx.) kg/km: 396 Cu Index: 201.9
Item Index: 1669 008 33 Item Name: (N)HXCH-J-SERVO FE180 PH90/E90 0,6/1 kV 4×6 CPR Class: B2ca-s2,d1,a1 Outer Diameter (approx.) mm: 17.3 Cable Weight (approx.) kg/km: 497 Cu Index: 285.4
Item Index: 1669 009 33 Item Name: (N)HXCH-J-SERVO FE180 PH90/E90 0,6/1 kV 4×10 CPR Class: B2ca-s2,d1,a1 Outer Diameter (approx.) mm: 20.1 Cable Weight (approx.) kg/km: 739 Cu Index: 469.5
Item Index: 1669 010 33 Item Name: (N)HXCH-J-SERVO FE180 PH90/E90 0,6/1 kV 4×120 CPR Class: Outer Diameter (approx.) mm: 55.2 Cable Weight (approx.) kg/km: 6679 Cu Index: 5147.9
Item Index: 1669 001 33 Item Name: (N)HXCH-J-SERVO FE180 PH90/E90 0,6/1 kV 4×1,5 CPR Class: B2ca-s2,d1,a1 Outer Diameter (approx.) mm: 13.4 Cable Weight (approx.) kg/km: 251 Cu Index: 90.6
Item Index: 1669 002 33 Item Name: (N)HXCH-J-SERVO FE180 PH90/E90 0,6/1 kV 4×50 CPR Class: B2ca-s2,d1,a1 Outer Diameter (approx.) mm: 38.1 Cable Weight (approx.) kg/km: 2862 Cu Index: 2179.7
Item Index: 1669 003 33 Item Name: (N)HXCH-J-SERVO FE180 PH90/E90 0,6/1 kV 4×16 CPR Class: B2ca-s2,d1,a1 Outer Diameter (approx.) mm: 23.1 Cable Weight (approx.) kg/km: 1069 Cu Index: 739.5