Application
TECHNOFLAME NHXCH FE180 PH90/E90 0,6/1 kV fire resistant and halogen free power cables, are intended for power supply to fire protection equipment in objects of sharp fire protection requirements, particularly in fire alarm and fire automatic control systems. The cables shall be applied in locations where, in case of fire, higher safety for human beings and expensive electronic equipment is required (subway tunnels, hospitals, shopping centres, supermarkets, cinemas, theatres, stadiums and other public buildings). Functions of the cables are maintained for 90 minutes – power is supplied to equipment which must operate in fire conditions and during fire fighting (e.g. water pumps in fire extinguishing systems, smoke removing fans, emergency lighting and elevators). The cables are certified by Scientific and Research Centre for Fire Protection - National Research Institute (Centrum Naukowo-Badawcze Ochrony Przeciwpożarowej - PIB) at Józefów. The cables are flame retardant and their smoke emission is low, emitted fumes are non toxic and non corrosive. The cables are resistant to water in accordance with EN 50200 Annex E and can be used in fire protected rooms with fixed pressure water spraying fire extinguishing systems (sprinkler zones). The cables are suitable for fixed indoor and outdoor installations. Sheathing is UV radiation resistant. Laying cables in water or direct earth burial are only permitted if additional protection is used.Structure
- bare annealed copper conductors meeting requirements of PN-EN 60228 standard:
- mica tape and halogen free cross-linked compound insulation – colours:
- insulated conductors laid-up into a cable core,
- inner covering made of halogen free compound,
- concentric conductor formed by bare copper wires with counter helix of copper tape over the inner sheath,
- concentric conductor wrapped in polyester tape,
- orange cable sheath made of halogen free compound type HM4 according to HD 604 S1.
| Conductor cross-section | mm2 | 1,5 | 2,5 | 4 | 6 | 10 | 16 | 25 | 35 | 50 | 70 | 95 | 120 | 150 | 185 | 240 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Maximum DC conductor resistance at 20°C | Ω/km | 12,1 | 7,41 | 4,61 | 3,08 | 1,83 | 1,15 | 0,727 | 0,524 | 0,387 | 0,268 | 0,193 | 0,153 | 0,124 | 0,0991 | 0,0754 |
| Characteristics | Descritpion |
|---|---|
| Operating voltage Uo/U | 0,6/1 kV |
| Voltage test | 4 kV sk |
| Minimum insulation resistance, at90°C | 1011 Ω∙cm |
| Inductance, approximate | 0,7 mH/km |
| Conductor temperature limit in work conditions | + 90°C |
| Conductor temperature limit at short-circuit | + 250°C |
| Operating temperature range during operation | from - 30 to + 90°C |
| Operating temperature range during installation | from - 5 to + 70°C |
| Minimum bending radius | 15 x cable diameter |
| Corrosivity of emitted gases per | very low, halogen free PN-EN 60754-1, PN-EN 60754-2, |
| pH | > 4,3 |
| Conductivity | < 2,5 μS/mm |
| Smoke density | low smoke density PN-EN 61034-2, IEC 61034-2 |
| Light transmittance | 60-80 % |
| Cable combustibillity | flame retardant, o zmniejszonej palności |
| Combustibillity tests | PN-EN 60332-1-2, IEC 60332-1-2, PN-EN 60332-3-24, IEC 60332-3-24, |
| Circuit integrity: E90 | DIN 4102-12 |
| Circuit integrity: PH90 | PN-EN 50200 lub PN-EN IEC 60331-1 |
| Insulation integrity FE180 | IEC 60331-21, IEC 60331-11 |
| Reference standards | CNBOP-PIB- KOT- 2021/0311-3701 wyd.3, WT-TK-44 |
| Class reaction to fire ( PN-EN 13501-6) | B2ca-s1b,d0,a1 |
| DoP declarations are available at | technokabel.com.pl |
| The cable meets requirements of the low voltage direction | 2014/35/UE |